Two wire transmitter current input isolation distribution device
Provide isolated power voltage to the two-wire transmitter on site, and isolate and convert the 4-20mA signal generated by the transmitter before tran
Product details

Current signal input: 4-20mADC

Distribution voltage for transmitter (Up): ≤ 14.5V

Overload current: ≤ 28mA

Output current signal: 4-20mADC

Output circuit power supply (Ue): 20-30VDC

Voltage drop (Ud): ≤ 3V (20mA)


Output load capacity: see the following calculation diagram

二线制变送器电流输入隔离配电器.png

Output load resistance (RL): Calculation formula RL ≤ (Ue Ud Up) ÷ 0.02

Standard accuracy: ± 0.1%

Temperature drift: ± 0.015%/℃

Load variation impact: ± 0.1% F.S

Response time (0-90%, 100% -10%):<10ms

Isolation capability: 2.5KV, 1min, 50Hz between input-output

Insulation resistance: ≥ 100M Ω/500VDC between input and output

Working environment temperature: -10 to+60 ℃; Relative humidity ≤ 85%

Dimensions: 13 × 122 × 117mm (width × height × depth)