VIP member
Temperature monitoring system for factories and production workshops
Article Introduction:
Product details
1、 Purpose
Due to certain requirements for environmental temperature or internal temperature of equipment in some factories and production workshops, we hope to. Our company has developed and designed a temperature monitoring system for factories and production workshops that can monitor temperature in real-time. This system can monitor the environment within its workshopReal time temperature collection is carried out for equipment and cold storage, and the data is transmitted to a PC for data recording and analysis through software.
The influencing factors have been thoroughly investigated on site, and the main influencing factors are considered as follows:
1. The temperature inside the factory building is high, and there is a high requirement for waterproofing of the outer shell.
2. The temperature range for collection is relatively large, reaching -50 to 250 degrees Celsius;
The temperature monitoring system provided by Guangzhou Sibe Electronic Technology Co., Ltd. has environmental monitoring and alarm functions, and can be easily accessed through the network without any impact on the original system factory.
2、 Introduction to Main Equipment
SPD-200GSM-P environmental monitoring host, monitoring host, 485 acquisition module, temperature probe
| SPD-200GSM-P Environmental Monitoring Host Product Performance Parameters | |
| Switch quantity (dry contact) input |
4-channel switch input interface, photoelectric isolation, can be connected to sensors such as smoke detectors, water leaks, lightning protection detection, etc. The monitoring host can expand 4, 8, 16 and other switch input modules |
| Linkage output | 2-channel relay output interface, capable of achieving linked alarm output, light control, and more. |
| Analog input interface |
4-channel analog input interface, 4-20mA, 0-20mA current loop interface (Can be connected to load current meters, battery pack voltage meters, input voltage meters, output voltage meters, wind speed sensors, dust sensors, hydraulic and other sensors with 4-20mA). |
| Air conditioning control interface | One ordinary air conditioner infrared control interface can achieve automatic on/off control of one ordinary air conditioner. |
| Temperature and humidity (digital quantity) input |
One interface for temperature and humidity probes, enabling monitoring of one temperature and humidity monitoring point. The monitoring host can expand up to 64 channels of 485 temperature and humidity sensors |
| communication interface | 1 RS485 bus interface, compatible with multiple 485 bus modules. If UPS, precision air conditioning, fresh air fan, smoke exhaust fan and other equipment with 485 or 232 protocol are used, up to 32 485 bus modules can be connected, with a maximum transmission distance of 1200 meters. Through the RS485 interface, devices can be remotely upgraded with network firmware or debugged by manufacturers |
| Backup power interface | 12V battery backup power interface (automatically activated in case of unexpected power outage in the factory area) |
| SMS API | Support GSM SIM cards from China Mobile and China Unicom; It can achieve telephone voice alarm, SMS alarm, email alarm, software multimedia alarm, and on-site sound and light alarm. |
| power supply voltage | Device powered by DC. Default factory value: DC12V |
| Appearance description | Standard 19 inch 1U chassis, LCD screen display, diversified display content, replacing the disadvantage of single digital display. Equipped with a remote control, relevant alarm parameters can be set and viewed on site |
| Installation method | Rack mounted fixed installation |
3、 Topology diagram of environmental monitoring
application
Industrial site control
Remote monitoring and data collection
Power communication and monitoring
Electronic product manufacturing
single laneThermistor temperature isolation transmitter
Isolate and transmit various thermal resistance signals on site, and output 485 communication signals to the control system or other unit combination instruments. Signal isolation can effectively eliminate ground reflux, solve industrial interference and signal conversion transmission and matching problems.
lThis is a thermistor temperature transmitter with a one in one out isolator. This isolator adopts an independent DC power supply method, with isolation between the power supply input output.
Standard 35mm DIN rail card installation.
Power supply
Power supply voltage: 24VDC ± 10%
Current consumption:<60mA (when powered by 24VDC)
Power loss:<1.5W, (when powered by 24VDC)
L Input
Input signals: various types of thermal resistors such as Pt100, Pt10, Cu50, Cu100, etc
Lead resistance: ≤ 5 Ω
L Output
Output: RS485 communication MODBUS-RTU protocol.
Comprehensive main technical parameters
Standard accuracy: ± 0.2% F.S, ± 0.5% F.S
Temperature drift: ± 0.015%/℃
Response time:<0.03s (10~90%)
Stable time: ≤ 0.5s
Power supply variation impact:<± 0.1% (allowable voltage range)
Isolation withstand voltage: 2500VDC/min
Insulation resistance:>100M Ω
Communication distance: 1200m
Communication format: 9600, 8, n,1
Working environment temperature: -10~50 ℃
Working environment humidity: ≤ 85RH%
Storage environment temperature: -30~60 ℃
Dimensions: Width 16.6 x Height 105 x Depth 65 (mm) Shell Material: Flame retardant ABS+PC
Dustproof design: available
feature
Isolation transmission, 485 communication, standard MODBUS-RTU protocol.
Single channel, one in and one out.
Isolation between input output power supply.
Equipped with a working power indicator light.
Standard 35mm DIN rail card installation.
PT100 temperature sensor platinum thermistor
havepower and environment monitoring systemmonitoring systemprojectDo you need to move the ring?Just look for Sibe Technology, we have case studies to help you operate projects more easily.Please call: Or consult online!We provide free services for youDynamic environmental monitoring systemProposal and product quotation.
Online inquiry