Specification parameters
|
explain
|
Supply Voltage
|
20~35VDC
|
power consumption
|
(24V power supply, when relay contacts are closed):
≤1.2W(SWP7011)≤1W(SWP7013)
≤2.2W(SWP7111)≤1.8W(SWP7113)
≤2.4W(SWP7018)≤2.0W(SWP7019)
|
INPUT
|
Switch, proximity switch
Distribution voltage: ≈ 8V (open circuit) Short circuit current: ≈ 8mA
|
signal output
|
Relay output characteristics:
Response time: ≤ 20ms
Drive capability: 250V, A.C., 2A or 30V, D.C., 2A
Load type: resistive load
Transistor output characteristics:
External power supply: ≤ 40V, d.c., current output: ≤ 40mA (with short-circuit protection)
Transistor collector output: High level: VCC, Low level: ≤ 2.5V
Transistor emitter output: High level: VCC-2.5V, Low level: ≤ 0.5V
|
Input and output characteristics (when set to in-phase control)
|
On site switch closed or input circuit current>2.1mA, output relay closed, channel green indicator light on
On site switch open circuit or input circuit current<1.2mA, output relay open circuit channel green indicator light off
|
Input and output positive and negative phase control settings
|
When K2 is set to OFF, the disconnection detection function is turned on, and when it is set to ON, the disconnection detection function is turned off.
Note: When a switch is used as the input signal and disconnection detection is required, a 10K Ω resistor must be connected in parallel at both ends of the switch.
|
electromagnetic compatibility
|
Compliant with GB/T18268 Industrial Equipment Application Requirements
|
Environmental temperature for use
|
-20~+60℃
|
Connected on-site devices
|
NAMUR proximity switches, switches and other on-site equipment that comply with DIN19234
(including intrinsically safe pressure switches, temperature switches, liquid level switches, etc.)
|