Structural diagram of the new ZW7 electric high-voltage vacuum circuit breaker in Chengdu
Structural diagram of the new ZW7 electric operated high-voltage vacuum circuit breaker in Chengdu
The new ZW7-40.5 vacuum circuit breaker is smaller in size than the old ZW7, reduces space for easy installation, is lightweight and easy to transport, has a simple structure, fewer moving parts, and is completely suitable for pole mounted single bar connection.
ZW32 structural characteristics
1. The circuit breaker adopts a three-phase pillar structure, which has the characteristics of stable and reliable breaking performance, no combustion and explosion hazards, maintenance free, small size, light weight, and long service life.
2. The circuit breaker adopts a fully enclosed structure with good sealing performance, which helps to improve moisture-proof and anti condensation performance, especially suitable for use in cold or humid areas.
3. The three-phase pillars and current transformers adopt imported outdoor epoxy resin solid insulation, or indoor epoxy resin wrapped with organic silicon rubber solid insulation; It has the characteristics of high and low temperature resistance, UV resistance, and aging resistance.
4. Circuit breakers can be equipped with two-phase or three-phase current transformers for overcurrent or short-circuit protection, and can also provide current acquisition signals to intelligent controllers; According to user requirements, measuring current transformers can be installed.
5. The circuit breaker can be equipped with a three-phase interlocking isolation switch, which has a visible fracture when the isolation switch is in the open state, and has an anti misoperation interlock device with the circuit breaker body. The circuit breaker can only be operated when the isolation switch is fully closed or fully opened. Can be connected to lightning arrester post insulators for easy maintenance.
Technical Parameter
Main technical parameters of circuit breaker
Serial number |
Project |
unit |
Numerical value |
1 |
rated voltage |
kV |
40.5 |
2 |
Rated current |
A |
1250/1600/2000/2500 |
3 |
Rated frequency |
Hz |
50 or 60 |
4 |
Power frequency withstand voltage for 1 minute (wet) (dry) Interphase, ground/fracture |
kV |
80 95/95 |
5 |
Lightning impulse withstand current (peak value) Interphase, ground/fracture |
kV |
185 |
6 |
Rated short circuit breaking current |
kA |
25/31.5 |
7 |
Rated short-circuit closing current (peak) |
kA |
63/80 |
8 |
Rated peak withstand current |
kA |
63/80 |
9 |
4S short-time withstand current |
kA |
25/31.5 |
10 |
Rated operating cycle |
Split -0.1s - Split -3s - Split -6s - Split -60s Recovery |
|
11 |
Rated short-circuit current breaking times |
order |
30 |
12 |
mechanical life |
order |
10000 |
13 |
Institutional control voltage |
V |
AC/DC220 |
14 |
Secondary circuit 1-minute power frequency withstand voltage |
KV |
2 |
Main mechanical parameters of circuit breakers
Serial number |
Parameter |
unit |
Data |
1 |
clearance between open contacts |
mm |
18±1 |
2 |
Contact overtravel |
mm |
4±0.5 |
3 |
opening speed |
m/s |
1.4-1.8 |
4 |
closing speed |
m/s |
0.4-0.8 |
5 |
Contact closing bounce time |
ms |
≤5 |
6 |
Center distance between phases |
mm |
710±2 |
7 |
Three phase opening and closing asynchrony |
ms |
≤2 |
8 |
Resistance of each phase conductive circuit |
μΩ |
<80 |
9 |
close time |
ms |
≤100 |
10 |
Opening time |
ms |
≤50 |
11 |
weight |
Kg |
About 800 |
35KV Outdoor High Voltage Vacuum Circuit Breakerzone of application
Zhejiang Province, Jiangsu Province, Anhui Province, Shanghai City, Shandong Province, Hebei Province, Henan Province, Beijing City, Tianjin City, Shandong Province, Liaoning Province, Heilongjiang Province, Jilin Province, Inner Mongolia Autonomous Region, Shanxi Province, Shaanxi Province, Gansu Province, Autonomous Region, Xizang Autonomous Region, Qinghai Province, Yunnan Province, Guangxi Autonomous Region, Sichuan Province, Guizhou Province, Chongqing City, Hubei Province, Hunan Province, Jiangxi Province, Guangdong Province and other regions.
35KV Outdoor High Voltage Vacuum Circuit Breakerpurchasing process
1. Purchasing department, inform the product specifications, models, and quantities
2. Communicate with the technical department to confirm the drawings and verify the parameters
3. The Ministry of Commerce drafts contracts based on technical agreements and places orders for production
4. The production department produces according to the drawing parameters of the technical department and the order table of the business department
5. Shipping Department Customer Delivery Address and Method - Shipping
6. Receipt follow-up: Salespeople promptly follow up on customer receipt and provide feedback to the company
7. Follow up on customer satisfaction with product usage in the office, conduct market research to better serve customers and the market
Structural diagram of the new ZW7 electric high-voltage vacuum circuit breaker in Chengdu