Overview
Name |
ID |
Product Description |
Δpmax |
Δps |
kvsRated flow coefficient when the valve is fully open |
nominal diameter |
|---|---|---|---|---|---|---|
MVF461H15-0.6 |
100325519 |
Two way electromagnetic regulating seat valve, flange connection, PN16, DN15, kvs 0.6, AC/DC 24 V |
1000 kPa |
1000 kPa |
0.6 m3/h |
15 |
MVF461H15-1.5 |
100325520 |
Two way electromagnetic regulating seat valve, flange connection, PN16, DN15, kvs 1.5, AC/DC 24 V |
1000 kPa |
1000 kPa |
1.5 m3/h |
15 |
MVF461H15-3 |
100325521 |
Two way electromagnetic regulating seat valve, flange connection, PN16, DN15, kvs 3, AC/DC 24 V |
1000 kPa |
1000 kPa |
3 m3/h |
15 |
MVF461H20-5 |
100325522 |
Two way electromagnetic regulating seat valve, flange connection, PN16, DN20, kvs 5, AC/DC 24 V |
1000 kPa |
1000 kPa |
5 m3/h |
20 |
MVF461H25-8 |
100325523 |
Two way electromagnetic regulating seat valve, flange connection, PN16, DN25, kvs 8, AC/DC 24 V |
1000 kPa |
1000 kPa |
8 m3/h |
25 |
MVF461H32-12 |
100325524 |
Two way electromagnetic regulating seat valve, flange connection, PN16, DN32, kvs 12, AC/DC 24 V |
1000 kPa |
1000 kPa |
12 m3/h |
32 |
MVF461H40-20 |
100325525 |
Two way electromagnetic regulating seat valve, flange connection, PN16, DN40, kvs 20, AC/DC 24 V |
1000 kPa |
1000 kPa |
20 m3/h |
40 |
MVF461H50-30 |
100325526 |
Two way electromagnetic regulating seat valve, flange connection, PN16, DN50, kvs 30, AC/DC 24 V |
1000 kPa |
1000 kPa |
30 m3/h |
50 |

function
BPZ:MVF461H..
Continuous regulating electromagnetic control valve for high-temperature hot water and steam
A two-way electromagnetic control valve used for analog regulation of high-temperature hot water and steam, PN 16 , Equipped with positioning control, valve position feedback, spring reset, and manual function

technical specifications
rated pressure |
PN 16 |
Working Voltage |
AC 24 V ; DC 20...30 V |
Positioning signal |
DC 0...10 V; DC 0...20 mA; DC 2...10 V; DC 4...20 mA; DC 0...20 V Phs |
positioning time |
<2 s |
Equipped with spring reset function |
A ->AB closed |
position feedback |
DC 0...10 V; DC 2...10 V; DC 0...20 mA; DC 4...20 mA |
Protection level |
IP31 |
ambient temperature |
-5...45 °C |
Installation location |
Vertical to horizontal |
Allow work pressure |
Water<120 ° C: 1600 kPa |
leakage rate |
<0.05% kvsvalue |
Absolute pressure p1 steam |
900 kPa ABS |
medium temperature |
1...180 °C |
Valve flow characteristics |
Equal percentage; linear |
Travel accuracy Δ H/H100 |
1:1000 |
valve body |
Ductile iron EN-GJS-400-18-LT |
Valve internal material |
Chromium nickel steel |
Technical Specifications Table |
N4361 |