Nantong Zhancheng Electromechanical Equipment Co., Ltd
Home>Products>SH2 Programmable Controller
Firm Information
  • Transaction Level
    VIP member
  • Contact
  • Phone
    13862733021
  • Address
    Nantong Industrial Expo City 4-103
Contact Now
SH2 Programmable Controller
Performance features: 32 points, 48 points, and 64 points for the main body, 8 points and 16 points for the expansion module, with a maximum configura
Product details
Performance Features:

The main body has 32 points, 48 points, and 64 points, the expansion module has 8 points and 16 points, and the maximum configuration of I/O points is 80 points
Processing speed: average 4.7us/language, 3ms/500 language
Number of data registers: 1024 words, excluding T/C values, special registers
User program capacity: 2.5K languages, EEPROM storage
There are two types of working power supply models: AC85~264V and DC24V; AC models provide 24V power supply for sensors
The entire series of products come with one RS232 communication port, which can complete A-type, B-type, CCM2, and protocol free communication functions
SH2 adds an RS485 communication port compared to SH1, supporting MODBUS RTU communication and Mode 70 protocol free communication

Performance specifications:

project
SH1/2-32
SH1/2-48 SH1/2-64
I/O transmission method
Simultaneous transmission method, direct output and interruption function
programming language
Trapezoidal diagram and hierarchical sharing
Instruction type

135 records (52 in sequence, 23 in control, 60 in data processing) (SH2:136 records)

processing speed
An average of 4.7 USD/language, 3ms/500 language
Power outage maintenance
Optional battery addition
Number of data registers
1024 words, excluding T/C values, special register
User program capacity
2.5K language, EEPROM storage
I/O point count
32 points (basic)
40 or 48 points (with extension)
48 points (basic)
56 or 64 points (with extension)
64 points (basic)
72 or 80 points (with extension)
Number of internal coil points
256 points
level
256 points
Shift register (R)
Internal coil as displacement object
Timer (T)
128 points (0.1s 0.01s)
Counter (C)
128 points (0-9999)
Timed scanning interval setting
(0-99) * 2ms can be set
protection method
Password function
Special Input/Output Function
Software filtering input 4 points (0-99) x 2ms can be set
High speed counter/external interrupt 2 points, counting speed 2KCPS (SH2:5KCPS), can form 8 modes
communication function
SH1/SH2: RS-232C communication port, supporting A-type, B-type, CCM2 (substation) and protocol free communication functions;
SH2: RS-485 communication port, supporting MODBUS RTU communication and Mode 70 protocol free communication.



Model List:

model type model type power supply
SH1/2-32R1 16:00 24VDC/16:00 relay SH1/2-48R1 24 o'clock 24VDC/24 o'clock relay AC85-264V
SH1/2-32T1 16:00 24VDC/16:00 transistor SH1/2-48T1 24 point 24VDC/24 point transistor
SH1/2-32R1-C 16:00 24VDC/16:00 relay SH1/2-48R1-C 24 o'clock 24VDC/24 o'clock relay DC24V
SH1/2-32R2 20 o'clock 24VDC/12 o'clock relay SH1/2-48R2 28pm 24VDC/20pm relay AC85-264V
SH1/2-48T1-C 24 point 24VDC/24 point transistor DC24V
SH1/2-32R2-C 20 o'clock 24VDC/12 o'clock relay SH1/2-48R2-C 28pm 24VDC/20pm relay
SH1/2-48T2-C 28 point 24VDC/20 point transistor
SH1/2-64R1 32 point 24VDC/32 point relay SH1/2-64R2 36pm 24VDC/28pm relay AC85-264V
SH1/2-64R1-C 32 point 24VDC/32 point relay SH1/2-64R2-C 36pm 24VDC/28pm relay DC24V


Expansion unit:

model I/O type power supply
H1-16ND1 16:24 VDV input No power required
H1-16TR1 16 point relay output
H1-16 CDR1 8 o'clock 24VDC/8 o'clock relay
H1-4AD2DA 4 analog inputs/2 analog outputs
H1-4AD 4-channel analog input
H1-2DA 2-channel analog output



Communication:


RS-232C:
project Create a programming port As a communication port
signal RS-232C standard (non insulated)
Transmission speed 9600bps Special register settings
Transmission distance Below 3m Below 15m
connect Six pin telephone socket
connected device S-200HP DirectSoft software Serial communication equipment
data format HEX ASCII and HEX are optional
Bureau number fixed Special register settings
agreement Programmer specific protocol CCM2 protocol communication (slave function)
Type A/B, no protocol communication

RS-485:
project Instructions
signal Three wire RS-485 (non insulated)
Transmission speed Special register settings
connect 3-terminal desktop, supporting 1 to many connections
connected device Serial communication equipment
Transmission distance Below 1000 meters
data format Special register settings
agreement MODBUS RTU/No protocol
Bureau number MODBUS RTU station number 1-247


Dimensions (unit: mm):

model long wide tall
SH1/2-32 160 90 90
SH1/2-48 216
SH1/2-64 262

Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!