The WM261 transmitter can measure, convert, and simulate temperature and humidity signals for transmission. These two parameters are transmitted to the remote receiver through analog signals. This transmitter comes with a built-in sensing/conversion module
highlight
- Specially designed for high-precision measurement in controllable environments
- Output signal selectable
- Linearization of isotherms is optional
|
 |
technical indicators
|
|
performance |
| Humidity range |
0-100% RH |
| Temperature range |
-20 ~ +80°C |
| Humidity accuracy |
<±2% RH (5–95% RH) |
| temperature accuracy |
Pt100 1/3DIN direct ±0.2°C Current output ± 0.3 ° C |
| Humidity stability |
<± 1% RH/year |
| response time |
T90<10 seconds |
|
Input/Output |
Humidity output signal Can be configured according to requirements |
4–20 mA 0–1, 0–5, 0–10 V |
Temperature output signal Can be configured according to requirements |
4–20 mA 3-wire 1/3 DIN Pt100 0–1, 0–5, 0–10 V |
| power supply voltage |
| Output 4-20 mA: |
V + = 12–30 V DC |
| Output 0-10 V: |
V + = 15–30 V DC |
| Output 0-5 V: |
V + = 10–30 V DC |
| Output 0-1 V: |
V + = 8–30 V DC |
|
| load resistor |
| Output 4-20 mA: |
Rload< (Uv-9)/0.02 |
| Output 0-10 V: |
R > 10 kΩ |
| Output 0-5 V: |
R > 5 kΩ |
| Output 0-1 V: |
R > 1 kΩ |
|
| Current consumption |
Maximum 2x20 mA |
|
operating condition |
Operating Humidity S sensing element Shell, storage |
0-100% RH (non condensing) 0-98% RH (non condensing) |
Operating Temperature measurement end shell store |
-30 ~ +85°C -30 ~ +70°C -40 ~ +70°C |
|
mechanical properties |
| Sealing protection level |
IP65 (NEMA 4 level) |
| Shell material |
PPO |
size Shell: Probe: |
880 x 80 x 34mm L=85mm, ø12mm |
| electrical connection |
Threaded compression terminal |
| weight |
100g |
|
|
|
|
|
|