installation
1. A multi stranded copper wire with a power connection wire of not less than 10mm2, and a multi stranded copper wire with a grounding connection wire of not less than 16mm2. The connecting wire should be as short, straight, and thick as possible.
2. The front end of the lightning arrester should be connected in series with suitable backup protectors, fuses, or air switches. -
Installation precautions
1. During installation, the power must be disconnected and live operation is strictly prohibited. The connecting wires must meet the requirements.
2. After installation, insert the lightning protection module into place and check if it works properly.
3. When the module fault display window of the lightning arrester indicates red (the remote signaling terminal outputs an alarm signal), it indicates that the lightning arrester has malfunctioned and should be replaced in a timely manner.
4. The lightning arrester does not require special maintenance, it only needs to be regularly checked for loose connections and normal status indicators.