Positive pressure integrated chlorine dioxide generator manufacturer direct sales customization
The principle and composition of a positive pressure chlorine dioxide generator are the same as those of a standard chlorine dioxide generator, but due to the fact that a negative pressure chlorine dioxide generator requires non pressure feeding, a positive pressure equipment is needed for the feeding point with pressure. Performance characteristics: The inner chamber of the equipment is made of high temperature and pressure resistant titanium alloy material, without the need for a power water source, with a safety and explosion-proof system, safe and reliable
Handling methods for minor malfunctions of chlorine dioxide generator:
1. The burette is not feeding: When the reactor is first turned on, there is no water added or there are too many impurities in the raw material box, causing the burette to be blocked. It is necessary to add water or clear the burette, clean the raw material box, and check the safety valve.
2. Hydrochloric acid cannot be pumped in: Insufficient negative pressure or air leakage at pipeline interfaces and valves, requiring adjustment of water pressure or inspection of pipeline interfaces and valves for air leakage; Check if the operation is carried out according to the regulations.
3. The equipment has no negative pressure, manifested as the burette not feeding and no bubbling sound heard inside the equipment. The reason is that the power water pressure is insufficient, and there is no pressure difference before and after the water injector, which cannot drive the water injector to work. The water pressure needs to be adjusted; The safety valve has been opened and needs to be reset; Pipeline interface and valve leakage.
4. When it is found that the burette is struggling to rotate, the "O" ring should be replaced in a timely manner.
5. The water temperature is too high (over 50)
(1) If the temperature display exceeds the set temperature and continues to rise, it indicates that the temperature display is broken. The power should be turned off immediately and the display should be replaced. It may also be due to poor contact of the connectors, causing the instrument display to be chaotic.
(2) When the water temperature is very high, but the temperature display instrument shows a temperature much lower than the set temperature (about 23), the reason is often due to wiring errors between the temperature display instrument and the liquid level controller. Please replace the wiring.