PT100/PT1000/thermocouple four channel temperature control instrument (can be equipped with RS485)
1、 Technical performance
1. Input type: CU50 (-50.0-150.0 ℃), Pt100 (-19.9-600.0 ℃) 、 Pt100 (-19.9-600.0 ℃)
K(0~1300℃)、E(0~700.0℃)、J(0~900.0℃)、S(0~1600℃)、T(-50.0~400.0℃)
Note 1: When the user places an order specifying input signals of 0-5V and 1-5V analog signals, the instrument no longer supports the input of various thermocouple and thermistor signals mentioned above,
Note 2: This instrument is a multi-channel instrument that can connect multiple sensors. But isolated sensors must be selected. Taking a thermocouple as an example: both wires of the thermocouple
Cannot conduct with metal casing. Otherwise, there may be situations such as inaccurate temperature measurement.
2. Control methods: Two position control, PID control
3. Output mode: Relay
4. Measurement accuracy: ± 0.5F • S ± 1 word, additional cold end calibration error ± 1 ℃
5. Working power supply: 220V AC power consumption: less than 4W
6. Working environment: 0~50 ℃, relative humidity ≤ 85% RH, non corrosive and non strong electromagnetic radiation environment
7. Dimensions: 160 × 80 × 110mm Hole size: 152 × 76mm
96 × 96 × 110mm hole size: 92 × 92mm
2、 Instrument panel
3、 Instrument wiring (for reference only, based on the wiring diagram on the instrument)
4、 Instrument usage
1First level menu settings
Press the function key(SETKey)3In seconds, enter the first level menu, and at this point, '...'1Road display window 'and' Section '2The 'road display window' displays parameter symbols and parameter values respectively. You can press the ◄ (shift key), ▲, and ▼ keys to change the parameter values. After modification, pressSETSave key to enter the next parameter; Modify other parameters using the same method.
2Secondary menu settings
Each channel parameter is adjusted according toCH1TheCH2TheCH3TheCH4Three seconds to enter the corresponding channel menu item, you can press the ◄, ▲, ▼ keys to change the parameter values. After completing the modification, pressSETSave key to enter the next parameter; The parameters are shown in the table below:
|
Primary Menu,Press the function key(SETKey)3Enter in seconds |
||||||||
|
serial number |
prompt |
Storage address |
name |
set the scope |
Instructions |
factory default |
||
|
one level dish single |
0 |
LOCK |
0000H |
combination lock |
0~50 |
Password lock is18When allowed to modify all Parameter, not for18It is prohibited to modify all parameters at this time |
18 |
|
|
1 |
Sn |
0001H |
Enter specifications |
0~4 |
CU50ThePt100TheKTheETheJTheSTheT |
|
||
|
2 |
ALP |
0002H |
Alarm definition |
0~4 |
0: No alarm; 1: Upper limit alarm 2: Lower limit alarm; 3Alarm outside the interval 4Alarm reported within the interval |
1 |
||
|
3 |
t |
0003H |
Output cycle |
0~120 S |
Set the action cycle for relay control |
20 |
||
|
4 |
S |
dp |
0004H |
0decimal point position1 |
0. ~No decimal point 1.; |
0 |
||
|
5 |
There is a decimal point |
P-SH |
0005H |
Set the upper limit of the valueP-SL |
~Full range |
This parameter limits the upper limit of the set value |
||
|
6 |
random |
P-SL |
0006H |
Lower limit of set valueRange starting point~ |
P-SH |
This parameter limits the lower limit of the set value |
||
|
7 |
random |
OPB |
0007H |
0Secondary output mode2 |
0.~Unpaid output;1.RS485 2.serial communication |
0 |
||
|
8 |
Equipped with micro typing function |
Add |
0008H |
1address64 ~1(9999~ |
Score)The numbering of instruments in the centralized control system(When equipped with micro printing function, set the printing interval time |
1 |
||
|
9 |
) |
bt |
0009H |
0Baud rate3 |
0~1200: 1;2400: 3;4800: 4;9600 |
9600 |
||
|
:submenu,pressCH13key |
||||||||
|
Enter in seconds
submenu one |
10 |
Channel parameter setting |
SP1 |
1000AH |
Channel control point settingScope byP-SLTheP-SH |
1decide |
Channel control point temperature setting parameters |
|
|
11 |
random |
AL1 |
000BH |
Alarm setting valueScope byP-SLTheP-SH |
decidefromAL-P |
Parameters determine the alarm mode |
||
|
12 |
random |
SC1 |
000CH |
Error correction value20.0 |
± |
0 |
||
|
13 |
Error correction value of sensor |
P1
|
000DH |
0Proportional band200.0
|
~The proportional band determines the magnitude of the system's proportional gain, PThe larger,The smaller the effect of proportion,The smaller the overshoot, But if it's too small, it will increase. warm-up time(P=0At this time, the instrument will switch to two position control,Some actuators that are not suitable for frequent start-up, such as fans, compressors, motors, etc., should use this method. Please refer to the parameters for detailsHY1The explanation section |
15.0 |
||
|
14 |
) |
I1 |
000EH |
0integration time3000 |
~Set the integration time to eliminate residual deviations caused by proportional control, Too much will delay the time for the system to reach equilibrium |
240 |
||
|
15 |
Too small can cause fluctuations |
D1 |
000FH |
0Differential time~ |
200SSet differential time to prevent output fluctuations, Improve control |
30 |
||
|
16 |
Stability of the system |
Hy1 |
0010H |
0.1Main control and alarm return difference50.0
|
~When the instrument is a two position control (proportional band)P=0) The dead zone between the opening or closing of the actuator to avoid frequent actions of the actuator. When the main control is in heating mode:When measuring valuesPV1≤ Set valueSV1-HY1When the actuator opens, whenPV1≥SV1+HY1 |
1.0 |
||
|
17 |
The actuator is turned off. |
At1 |
0011H |
0Self-tuning parameters1 |
0~ 1: Disable self-tuning |
0 |
||
|
|
18 |
: Enable self-tuning |
CoL1 |
0012H |
0Heating and cooling options1 |
0~ 1Heating function |
0 |
|
|
Cooling functionpressCH23key |
||||||||
|
Enter in seconds two |
19 |
Channel parameter setting |
SP2 |
0013H |
|
|
|
|
|
20 |
Ditto. |
AL2 |
0014H |
|
|
|
||
|
21 |
Ditto. |
SC2 |
0015H |
|
|
|
||
|
22 |
Ditto. |
P2 |
0016H |
|
|
|
||
|
23 |
Ditto. |
I2 |
0017H |
|
|
|
||
|
24 |
Ditto. |
D2 |
0018H |
|
|
|
||
|
25 |
Ditto. |
Hy2 |
0019H |
|
|
|
||
|
26 |
Ditto. |
At2 |
001AH |
|
|
|
||
|
|
27 |
Ditto. |
CoL2 |
001BH |
|
|
|
|
|
Ditto.pressCH33key |
||||||||
|
Enter in seconds three |
28 |
Channel parameter setting |
SP3 |
001CH |
|
|
|
|
|
29 |
Ditto. |
AL3 |
001DH |
|
|
|
||
|
30 |
Ditto. |
SC3 |
001EH |
|
|
|
||
|
31 |
Ditto. |
P3 |
001FH |
|
|
|
||
|
32 |
Ditto. |
I3 |
0020H |
|
|
|
||
|
33 |
Ditto. |
D3 |
0021H |
|
|
|
||
|
34 |
Ditto. |
Hy3 |
0022H |
|
|
|
||
|
35 |
Ditto. |
At3 |
0023H |
|
|
|
||
|
|
36 |
Ditto. |
CoL3 |
0024H |
|
|
|
|
|
Ditto.pressCH43key |
||||||||
|
Enter in seconds four |
37 |
Channel parameter setting |
SP4 |
0025H |
|
|
|
|
|
38 |
Ditto. |
AL4 |
0026H |
|
|
|
||
|
39 |
Ditto. |
SC4 |
0027H |
|
|
|
||
|
40 |
Ditto. |
P4 |
0028H |
|
|
|
||
|
41 |
Ditto. |
I4 |
0029H |
|
|
|
||
|
42 |
Ditto. |
D4 |
002AH |
|
|
|
||
|
43 |
Ditto. |
Hy4 |
002BH |
|
|
|
||
|
44 |
Ditto. |
At4 |
002CH |
|
|
|
||
|
|
45 |
Ditto. |
CoL4 |
002DH |
|
|
|
|
Ditto.
5、 Self tuning operationFirst, set the settings and then enter the menu,
Set the hysteresis to around 0.5-1 and AT to 1. The instrument enters a self-tuning state, and the corresponding display window flashes to show the "AT" character. At this time, the instrument is in positional control. After three oscillations, the instrument determines new parameters such as P, I, D and saves them. The instrument resets and enters the control state.
6、 Error message
1.
When the instrument window displays "HH or LL", please check if the sensor wiring is correct.