PT100/PT1000/thermocouple four channel temperature control instrument (can be equipped with RS485)
The YY-F460 instrument is a four channel intelligent temperature control instrument that can be simultaneously equipped with four PT100/PT1000 tempera
Product details

PT100/PT1000/thermocouple four channel temperature control instrument (can be equipped with RS485)

PT100/PT1000温度控制仪器表

1、 Technical performance
1. Input type: CU50 (-50.0-150.0 ℃), Pt100 (-19.9-600.0 ℃) 、 Pt100 (-19.9-600.0 ℃)
K(0~1300℃)、E(0~700.0℃)、J(0~900.0℃)、S(0~1600℃)、T(-50.0~400.0℃)
Note 1: When the user places an order specifying input signals of 0-5V and 1-5V analog signals, the instrument no longer supports the input of various thermocouple and thermistor signals mentioned above,
Note 2: This instrument is a multi-channel instrument that can connect multiple sensors. But isolated sensors must be selected. Taking a thermocouple as an example: both wires of the thermocouple
Cannot conduct with metal casing. Otherwise, there may be situations such as inaccurate temperature measurement.
2. Control methods: Two position control, PID control
3. Output mode: Relay
4. Measurement accuracy: ± 0.5F • S ± 1 word, additional cold end calibration error ± 1 ℃
5. Working power supply: 220V AC power consumption: less than 4W
6. Working environment: 0~50 ℃, relative humidity ≤ 85% RH, non corrosive and non strong electromagnetic radiation environment
7. Dimensions: 160 × 80 × 110mm Hole size: 152 × 76mm
96 × 96 × 110mm hole size: 92 × 92mm
2、 Instrument panel

PT1000智能温度控制器

3、 Instrument wiring (for reference only, based on the wiring diagram on the instrument)

PT100/PT1000/K型热电偶温度传感器

4、 Instrument usage


1First level menu settings

Press the function key(SETKey)3In seconds, enter the first level menu, and at this point, '...'1Road display window 'and' Section '2The 'road display window' displays parameter symbols and parameter values respectively. You can press the ◄ (shift key), ▲, and ▼ keys to change the parameter values. After modification, pressSETSave key to enter the next parameter; Modify other parameters using the same method.

2Secondary menu settings

Each channel parameter is adjusted according toCH1TheCH2TheCH3TheCH4Three seconds to enter the corresponding channel menu item, you can press the ◄, ▲, ▼ keys to change the parameter values. After completing the modification, pressSETSave key to enter the next parameter; The parameters are shown in the table below:

Primary Menu,Press the function key(SETKey)3Enter in seconds

serial number

prompt

Storage address

name

set the scope

Instructions

factory default

one

level

dish

single

0

LOCK

0000H

combination lock

050

Password lock is18When allowed to modify all

Parameter, not for18It is prohibited to modify all parameters at this time

18

1

Sn

0001H

Enter specifications

04

CU50ThePt100TheKTheETheJTheSTheT

2

ALP

0002H

Alarm definition

04

0: No alarm; 1: Upper limit alarm

2: Lower limit alarm; 3Alarm outside the interval

4Alarm reported within the interval

1

3

t

0003H

Output cycle

0120 S

Set the action cycle for relay control

20

4

S

dp

0004H

0decimal point position1

0. No decimal point 1.;

0

5

There is a decimal point

P-SH

0005H

Set the upper limit of the valueP-SL

~Full range

This parameter limits the upper limit of the set value

6

random

P-SL

0006H

Lower limit of set valueRange starting point~

P-SH

This parameter limits the lower limit of the set value

7

random

OPB

0007H

0Secondary output mode2

0.Unpaid output;1.RS485

2.serial communication

0

8

Equipped with micro typing function

Add

0008H

1address64

19999

Score)The numbering of instruments in the centralized control system(When equipped with micro printing function, set the printing interval time

1

9

)

bt

0009H

0Baud rate3

01200 12400 34800 49600

9600

submenu,pressCH13key

Enter in seconds

submenu

one

10

Channel parameter setting

SP1

1000AH

Channel control point settingScope byP-SLTheP-SH

1decide

Channel control point temperature setting parameters

11

random

AL1

000BH

Alarm setting valueScope byP-SLTheP-SH

decidefromAL-P

Parameters determine the alarm mode

12

random

SC1

000CH

Error correction value20.0

±

0

13

Error correction value of sensor

P1

000DH

0Proportional band200.0

The proportional band determines the magnitude of the system's proportional gain, PThe larger,The smaller the effect of proportion,The smaller the overshoot,

But if it's too small, it will increase. warm-up time(P=0At this time, the instrument will switch to two position control,Some actuators that are not suitable for frequent start-up, such as fans, compressors, motors, etc., should use this method. Please refer to the parameters for detailsHY1The explanation section

15.0

14

)

I1

000EH

0integration time3000

Set the integration time to eliminate residual deviations caused by proportional control,

Too much will delay the time for the system to reach equilibrium

240

15

Too small can cause fluctuations

D1

000FH

0Differential time

200SSet differential time to prevent output fluctuations,

Improve control

30

16

Stability of the system

Hy1

0010H

0.1Main control and alarm return difference50.0

When the instrument is a two position control (proportional band)P=0)

The dead zone between the opening or closing of the actuator to avoid frequent actions of the actuator. When the main control is in heating mode:When measuring valuesPV1≤ Set valueSV1-HY1When the actuator opens, whenPV1SV1+HY1

1.0

17

The actuator is turned off.

At1

0011H

0Self-tuning parameters1

0 1: Disable self-tuning

0

18

: Enable self-tuning

CoL1

0012H

0Heating and cooling options1

0 1Heating function

0

Cooling functionpressCH23key

Enter in seconds

two

19

Channel parameter setting

SP2

0013H

20

Ditto.

AL2

0014H

21

Ditto.

SC2

0015H

22

Ditto.

P2

0016H

23

Ditto.

I2

0017H

24

Ditto.

D2

0018H

25

Ditto.

Hy2

0019H

26

Ditto.

At2

001AH

27

Ditto.

CoL2

001BH

Ditto.pressCH33key

Enter in seconds

three

28

Channel parameter setting

SP3

001CH

29

Ditto.

AL3

001DH

30

Ditto.

SC3

001EH

31

Ditto.

P3

001FH

32

Ditto.

I3

0020H

33

Ditto.

D3

0021H

34

Ditto.

Hy3

0022H

35

Ditto.

At3

0023H

36

Ditto.

CoL3

0024H

Ditto.pressCH43key

Enter in seconds

four

37

Channel parameter setting

SP4

0025H

38

Ditto.

AL4

0026H

39

Ditto.

SC4

0027H

40

Ditto.

P4

0028H

41

Ditto.

I4

0029H

42

Ditto.

D4

002AH

43

Ditto.

Hy4

002BH

44

Ditto.

At4

002CH

45

Ditto.

CoL4

002DH

Ditto.

5、 Self tuning operationFirst, set the settings and then enter the menu

Set the hysteresis to around 0.5-1 and AT to 1. The instrument enters a self-tuning state, and the corresponding display window flashes to show the "AT" character. At this time, the instrument is in positional control. After three oscillations, the instrument determines new parameters such as P, I, D and saves them. The instrument resets and enters the control state.

6、 Error message

1.

When the instrument window displays "HH or LL", please check if the sensor wiring is correct.