Specification
Explosion proof mark: [Exib] IICT6
Input signal: (non local end)
Passive switch input: Switch type: Dry contact signal
Short circuit current: 8mA
Open circuit voltage: 8V
Active switch input: Input voltage ≤ 1V indicates' off '
Input voltage ≥ 4V indicates' on '

Output signal: (local safety end)
Passive relay switch output: Contact type: normally open (normally closed)
Contact capacity: 0.06A/24VDC
Passive collector open circuit output: External power supply: ≤ 24VDC
Switching frequency: 5KHz
Current output: ≤ 60mA
Active output equivalent circuit: Maximum output voltage: 26VDC
Minimum output voltage: 12VDC (output current 35mA)
Insulation resistance: ≥ 100M Ω (500VDC)
Insulation strength: intrinsic safety non intrinsic safety 2000V/min
Non intrinsic safety - Non intrinsic safety 1000V/min
Power consumption: ≤ 1.3 W
Power supply voltage: 24VDC ± 5%
Temperature drift: ≤ 0.01% FS/℃
Installation method: Rear mounted card (DIN35 rail)