overview
The NHR-6100R series paperless recorder (matching type) integrates multiple functions such as display, control, recording, and remote transmission, and can collect, store, and analyze important data in various industrial processes. It is mainly used in various industrial sites such as metallurgy, petroleum, chemical, building materials, papermaking, food, and pharmaceuticals.
instrument panel
|
|
|
| 160 * 80mm (Type A) | 80 * 160mm (Type B) | 96 * 96mm (Type C) |
|
① Display panel ② Confirm button ![]() Display channel switch key ![]() Time scale switch key ![]() ③ Cursor down key ④ Cursor up key ⑤ Left cursor shift key ⑥ Right cursor shift key |
|
Simple visual indication
|
|
Wiring diagram

Note 1: If different functions are marked on the same group of terminals in the wiring diagram, only one function can be selected.
If RS485 and RS232 are connected to the same set of terminals, only one can be selected.
Note 2: The direction of the wiring terminals on the back cover of the horizontal and vertical instruments is different, as shown in schematic diagram 1

instrument selectionNHR-61□R-□-□-□-□Paperless recorder ①②③③⑤
| ① Input channel | ② Specification and size | ||
| code | Channel | code | Width * Height * Depth |
|
01 |
1-channel input 2-channel input 3 inputs |
A B C |
160 * 80 * 110mm (horizontal) 80 * 160 * 110mm (vertical) 96 * 96 * 110mm (Method) |
| ③ Alarm output (Note 1) | ④ Power supply | ||
| code | Alarm channel (relay contact output) | code | Voltage range |
|
X |
no-output 1-limit alarm 2-limit alarm 3-limit alarm 4-limit alarm 5-limit alarm 6-limit alarm |
A D |
AC/DC 100~240V(AC/50-60Hz) DC 20~29V |
| ⑤ Additional functions (all of the following functions can be selected, separated by "/", functions that are not selected can be omitted) | |||
| Transmission output (Note 1) | Communication output | ||
| code | Output channel | code | Communication interface (communication protocol) |
|
1 2 3 |
1-channel transmission output 2-channel transmission output 3-channel transmission output |
D1 D2 D3 |
RS-485 communication interface (Modbus RTU) RS232 communication interface (Modbus RTU) RS232C printing interface |
| Feed output | |||
| code | Feed output (output voltage) | ||
| 1P 2P |
1-channel feeding output 2-channel feeding output |
||
| remarks: 1. Transmission output and alarm output can be combined, with transmission output and alarm output ≤ 6 2. Example of instrument model: Example 1: NHR-6101R-A-2-A-1/D1 (4-20mA input, 4-20mA output) Meaning: Single channel paperless recorder, with specifications of 160 * 80 * 110mm, 2-limit alarm output, AC100-240V power supply, 1-channel transmission output, RS485 communication. Input signal type (please specify the signal type when placing an order) |
| signal type | Range of measurement | signal type | Range of measurement |
| B S K E T J R N F2 Wre3-25 Wre5-26 Cu50 Cu53 Cu100 Pt100 BA1 |
400~1800℃ -50~1600℃ -100~1300℃ -100~1000℃ -100.0~400.0℃ -100~1200℃ -50~1600℃ -100~1300℃ 700~2000℃ 0~2300℃ 0~2300℃ -50.0~150.0℃ -50.0~150.0℃ -50.0~150.0℃ -200.0~650.0℃ -200.0~600.0℃ |
BA2 0~400Ω 0~350Ω 30~350Ω 0~20mV 0~100mV 0~20mA 0~10mA 4~20mA 0~5V 1~5V 0~10V 0-10mA square root 4-20mA square meter 0-5V square root 1-5V square root |
-200.0~600.0℃ -9999~99999 Special customization Special customization -9999~99999 -9999~99999 -9999~99999 -9999~99999 -9999~99999 -9999~99999 -9999~99999 Special customization -9999~99999 -9999~99999 -9999~99999 -9999~99999 |
| signal type | 4-20mA | 1-5V | 0-10mA | 0-5V | 0-20mA | 0-10V (specially customized) |
| Load resistance RL | RL≤480Ω | RL≥250KΩ | RL≤960Ω | RL≥250KΩ | RL≤480Ω | RL≥4KΩ |