If you need a Level 2 single-phase remote cost control intelligent energy meter (remote/switch built-in), please call 15388252881 for detailed parameters and prices
product overview
The DDZY121-A 2-level single-phase local cost control intelligent energy meter (remote/switch built-in) is an intelligent metering product that integrates carrier communication, energy metering, and CPU card local cost control. It can be combined with a concentrator and management system to form a centralized meter reading system, completing long-distance transmission of metering data and power on/off control. The performance indicators of this product meet the requirements GB/T17215.321-2008,GB/T17215.301-2007,DL/T698.1-2009,DL/T645-2007,Q/GDW364-2009 Waiting for the State Grid Corporation of China's relevant standards for smart energy meters.
Product parameters
Level 2 single-phase remote cost control intelligent energy meter
project | technical requirement |
reference voltage | 220V |
The specified working voltage range | 0.9Un~1.1Un |
Extended operating voltage range | 0.8Un~1.15Un |
Extreme working voltage range | 0.0Un~1.15Un |
Current measuring range | Direct access method 5 (60) A |
accuracy class | Active Level 2 |
operation temperature | -25℃~+60℃ |
working temperature limit | -40℃~+70℃ |
Relative temperature | 95% |
Frequency range | 50HZ |
starting current | 0.004Ib (rated voltage, rated frequency cos φ=1.0) |
Meter power consumption | Non communication state ≤ 1.5W, 10VA |
Communication status ≤ 3W, 12VA | |
MTBF | 10 Years |
Performance characteristics
The Level 2 single-phase remote cost control intelligent energy meter has positive and negative active energy metering functions and can store its data;
It has a complete multi rate settlement and billing function, and can set two sets of time periods, each set of time periods can set four rates;
Support modifying rate and time slot tables through infrared and RS485 communication interfaces;
The Level 2 single-phase remote cost control intelligent energy meter can read and remotely control the data of the energy meter through the 485 communication interface.