JCY-3 Building Materials Smoke Density Tester
1、 Scope of application:
The JCY-3 building material smoke density tester is developed according to the technical conditions specified in the national standard GB/T8627-2007 "Test Method for Smoke Density of Building Materials during Combustion or Decomposition", and is suitable for determining the static smoke production of building materials, their products, and other materials during combustion
2、 Functional Features
JCY-3 Touchscreen Smoke Density Tester for Building Materials Product Features
1. Building material smoke density tester with added touch screen control technology!The dual control mode of touch screen and computer is optional, allowing for both touch screen control and computer control, with strong logic and high intelligence.
2. The main and auxiliary burners can rotate automatically with accurate positioning.
3. Independently develop control programs that can meet various operations, recording, real-time curves, and result calculations in experiments.
4. Default touch screen control test, complete the test process with a light touch, and switch to computer control mode autonomously. The computer comes pre installed with software for testing.
3、 Related technical parameters
1. For the z-large smoke density (MSD) and smoke density grade (SDR) of the specimen: 0-100% continuously measurable, automatically calculated;
2. The correction error using standard light filter should not exceed 3%; Each device is equipped with three standard filters, which are representative of the data calibrated by the light source
3. The working pressure of the burner is (210 ± 5) KPa;
4. Apply flame to the sample for 4 minutes using a natural lamp;
5. Combustion lamp: It is a native lamp with a length of 260mm and a nozzle diameter of 0.13mm, forming a 45 ° angle with the smoke box;
6. Optoelectronic system: The light source is a bulb, with a power of 15W and a working voltage of 6V;
7. Exhaust system: This machine is equipped with a powerful exhaust fan, which can discharge exhaust gas outdoors after testing;
8. Smoke density measurement range: 0~100;
9. Accuracy of smoke density measurement: ± 3%;
10. Receiver: It is a silicon photovoltaic cell, with a transmittance of 0% indicating no light passing through, and a transmittance of 100% indicating complete unobstructed light passing through;
11. Main burner working pressure: 276KPa (adjustable);
12. Automatic timing, automatic ignition, automatic smoke exhaust; Luminous flux can be linearly calibrated in stages according to test data
More accurate;
13. touch screen:
a. Size: 5cunEffective display sizelong11Cm wide6.28cm;
b. resolving power:800*480
c. communication interfaceRS232, 3.3V CMOS or TTL, serial port mode
d. Storage capacity: 1G
e. Using pure hardware FPGA driver for display, with "zero" startup time, it can run immediately upon power on
f. Adopting M3+FPGA architecture, M3 is responsible for instruction parsing, FPGA focuses on TFT display, leading in speed and reliability compared to similar solutions
g. The main controller adopts low-energy processors and automatically enters energy-saving mode
14. Gas source: 95% propane gas, or gas of equivalent purity (provided by the customer);
15. Length * Width * Height 740 * 500 * Height 900 (mm)
4working conditions:
1. Environmental temperature: 0 ℃ -40 ℃;
2. Relative humidity: ≤ 85%
3. Power supply voltage and power: 220V ± 10%, 50HZ, 100W;
4. Gas pressure: 0-0.3MPa (adjustable);
5. Environmental and testing requirements: The instrument should avoid direct exposure or reflection of strong light during operation; After 90 minutes of testing, the gas source should be turned off to cool down the instrument for 15 minutes.
6. Environmental airflow: There is no forced air flow during operation;
7. The instrument should be tested in a fume hood;
5Instrument structure:
Divided into two main parts: smoke box and control;
Smoke box section: On the left and right panels of the smoke box, there are power switches, safety sign switches (backlight switches), gas regulating devices, and switches for controlling exhaust fans (fan switches).
VIDesign standards:GB/T8627-2007 "Test Method for Smoke Density of Building Materials during Combustion or Decomposition"
Compliant with standards:GB/T8627 ASTM D2843