Application scenarios:
Temperature transmitters are used to convert various input signals into 4-20mA output signals
● Input: Thermistor (RTD), Resistance (Ω), Thermocouple (TC), Voltage (mV) Product Features:
● High precision
● Output simulation
● Electrical isolation 2KV
● Can use two-wire technology, 4-20mA analog output
● Universal configurable type, operated and maintained through PC
Can be configured using USB
Technical Specifications:
Output signal: Analog 4-20mA
Supply voltage: U=7.5V~45V
Load: Max. (V power supply -7.5V)/0.022A (current output)
Alarm current: Below the measurement upper limit, the output drops to 3.8mA. Above the measurement upper limit, the output rises to 20.5mA
Sensor damage; The sensor circuit breaker output is 3.6mA or 22mA
Input current: ≤ 3.6mA
Current limit: ≤ 22mA
Environmental temperature: -40 to+85 ℃
Storage temperature: -40 to+100 ℃
Protection level: IP00, IP66 (installation)
Cold end compensation: Built in cold end compensation
Operation method: Adjust online through PC programming or PDA controller
Accuracy level: ≤ 0.2K or 0.08%
Measurement variables: temperature (temperature linear transfer), resistance, and voltage
Measurement range: The variation of the transmitter's measurement range depends on the sensor connection mode and input signal
Voltage influence: negligible
Environmental temperature impact: negligible (temperature drift)
Condensation: allowed
Seismic resistance: 4g/2-150Hz
Installation angle: unlimited