1.2. Stability: 6 months, ± 0.1% URL
1.3. Environmental temperature impact Zero point error: ± 0.2% URL/56 ℃ Overall error: ± (0.2% URL+0.18% calibration range)/56 ℃
1.4. Vibration impact: In any axial direction, the vibration effect at 200Hz is ± 0.05% URL/g
1.5. Power supply impact: Less than ± 0.005% output range/volt.
1.6. Load impact: There is no load impact unless there is a change in the power supply voltage.
1.7. Electromagnetic interference/radio frequency interference (EMI/RFI impact) When the field strength reaches 30V/M from 20 to 1000MHz, the output drift is less than ± 0.1% of the range.
1.8. Installation location impact The zero drift is at most ± 0.25kPa. All zero drift can be corrected; Has no impact on the measurement range.
2. Functional specifications 2.1. Measurement range:Refer to the selection table
2.2. Zero point and range It can be adjusted using the local range and zero buttons, or remotely using a HART controller
|
|
2.5. Damping time constant The time constant can be adjusted in increments of 0.1 seconds, from as small as 16.0 seconds.
2.6. Environmental temperature limit Without LCD meter head: -40 to 85 ℃ Equipped with LCD meter head: -30 to 60 ℃
2.7 . Process temperature limit Silicone oil filling: -40 to 104 ℃ Fill with inert liquid: -18 to 85 ℃
2.8. Storage temperature limit Without LCD meter head: -46 to 110 ℃ Equipped with LCD meter head: -40 to 70 ℃
2.9. ambient humidity 0-100% relative humidity
2.10. Overvoltage limit The transmitter will not be damaged when operating within the following limits: Measurement range up to 6.90MPa: 0-13.9MPa Measurement range up to 20.68MPa: 0-31.02MPa Measurement range up to 41.37 MPa: 0-51.71MPa
|