SF6High voltage switches are widely used high-voltage electrical appliances in power systems.SF6The reliable operation of high-voltage switches has become one of the most concerned issues for power supply and consumption departments.SF6Gas density meter is used to monitor operationSF6High voltage switch bodySF6The performance of an important component for gas density changes directly affects its qualitySF6The safe operation of high-voltage switches.
SF6Switch in a sealed containerSF6Gas pressure varies with temperature, usually20At ℃SF6The absolute pressure value is used asSF6The size of the gas density value. Measured at a certain ambient temperatureSF6Gas pressure values must be converted to their corresponding values20The equivalent pressure value at ℃ is used to determineSF6The safety of the switch.
Main technical parameters
Measurement range:0.01MPa~1.00 MPa
Measurement accuracy: ±0.2%(FS)
Rated density:0.60 MPa(Or pre-set according to device requirements)
Alarm threshold:0.52 MPa(Or pre-set according to device requirements)
Alarm release threshold:0.53 MPa(Or pre-set according to device requirements)
Locking threshold:0.50 MPa(Or pre-set according to device requirements)
Lock release threshold:0.51 MPa(Or pre-set according to device requirements)
Communication interface:RS485
Temperature measurement range:-50℃~100℃, measurement accuracy: ±0.2℃
Protection level:IP65
Working environment: Temperature-45℃~55℃, humidity ≤95%
Power Supply:AC220V±10% 50Hz±5%
main features
■ Fully enclosed design, easy to install and use, suitable for strong electromagnetic environments and outdoor environments
■ Industrial wide temperature rangeLCDLCD screen, easy to operate, all parameters and status are clear at a glance
■ High precision sensors accurately measure parameters such as pressure and temperature on site, and automatically convert them into20The pressure value at ℃ automatically compensates for temperature and pressure
■ The equipment adopts high reliabilityRS485Communication method, capable of long-distance transmission; Multiple devices form an online detection system for real-time monitoringSF6The density of the gas is measured and all data is transmitted in real-time to the data acquisition center to achieve centralized digital control
■ Users can change the rated density, alarm threshold, and lockout threshold of each device, and perform real-time parameter calibration and correction for each device online
■ On the computer in the data collection center, real-time data can be displayed and trend charts of status changes can be automatically drawn through software. The detection data can be saved for a long time to view the data more vividly and accurately