HC4000
The HC4000 controller adopts a modular design, which can accurately measure the haze (turbidity) of the medium. It has a menu style software and a mul
Product details
Users can configure parameters in HC4000 according to their specific process requirements

- Can connect multiple sensors
- Configurable multiple sets of parameters
- Provide multiple linearization tables
- Data Recorder
- Scattered light sensors have factory zero points
- Can be remotely controlled

display mode
- 1-4 simultaneous display values (adjustable)
- A digital bar chart displaying the set alarm values
- Trend Chart

Remote control
- Parameter settings
- zero calibration
- Status Hold
software tool
- 8 sets of parameters can be set (including range, alarm, display, etc.)
- 16 linearized tables (up to 11 points can be defined)
- 8 sets of compensation and gain values
- Automatic zeroing (local or remote)
- Factory zero point (only available for scattered light sensors)
- Password protection (Level 3 password or none)
- Memory (not easily lost) stores all configuration and recorded data


Technical Parameter


If there are any changes to the data, no further notice will be given.

PROFIBUS ® PA
- Meets the requirements of process automation application specifications (version 3.01)
- Circular data includes:
- 4 measurement results output, each measurement result has an alarm value and a status value
- Status values of 4 relays
- 2 input values
- Non cyclic data includes:
- Zero calibration, status maintenance, product switching, data from various monitors, fault codes
- Provide GSD, EDD files, and DTM required for FDT interface
- A coupler must be used from the PA interface to the DP interface

FOUNDATION ™ Fieldbus
- Compliant with FOUNDATION ™ Fieldbus H1 (IEC 61158-2) specification
- The functional modules include: 1 x RB, 8 x AI (s), 4 x DI (s), 2 x AO (s)
- H1 specification level: 31P, 32L
- H1 device level: basic device, link master device
- Output of 4 measurement results with status values
- 4 relay outputs with status values
- 2 input values
- Specific resource block parameters with optek: zero calibration, state maintenance, product switching
- Provide device description (DD) and performance files