Product details

Technical parameters:

Rated working pressure MPa)

1.0

Maximum allowable work pressure MPa)

1.2

Working pressure range MPa)

1.0-1.2

Rated flow rate L/s)

100

range m)

≥90

Horizontal swing angle °)

≥270

Self swinging angle(°)

80

maximumSpray angle(°)

120

Performance characteristics:

The PSKD10/100WB fixed fire monitor is fully functional, has a long range, and a large flow rate. The gun body and head can be remotely controlled from a distance. Beneficial for workers to stay away from the site, effectively avoiding harm to workers. The fire monitor is also equipped with a manual device for manual operation when there is no power supply. This cannon has the characteristics of small size, light weight, customizable base according to needs, easy operation, flexible and reliable, and convenient storage and transportation. Suitable for installation and use in oil fields, oil depots, airports, docks, large buildings, petrochemical tank areas, and other places, it is an indispensable equipment for fire safety supporting facilities.

usage method:

  

(1) Operating procedures

1. Install the fire monitor on the fixed flange and tighten the fixing screws to ensure good stability.

2. Connect the water supply pipeline.

3. Check whether the output terminals of the control box are reliably connected to the motor, and whether the battery power cord is reliably connected to the control box.

4. Press the power switch on the control box and press the remote control button to perform various operations.

(2) Introduction to various functions

1. DC and spray: press and hold the corresponding button of the control box or remote controller, the gun head will stretch from 0 to 40mm, and the water flow will change from spray to DC. Press and release the button to stop.

2. Move up and down: Press and hold the corresponding button on the control box or remote control, and the barrel will move from -15 ° to+85 °; Release the up and down buttons to stop, and the gun barrel will automatically stop when it reaches the end of its travel.

3. Left and right rotation: Press and hold the corresponding button on the control box or remote control, and the gun body will rotate within 270 degrees horizontally. Release the button to stop. The cannon body automatically stops when it reaches the end of its left and right travel.

4. Introduction to remote control functions; This remote control adopts a monochrome OLED display screen, which can display the remote control number, self swing angle, water cannon communication status, remote control battery level, water cannon pressure value, water cannon controller battery level, and corresponding button operations. And it has an automatic shutdown function.

(3) Shutdown

1. Use jog operation to extend and retract the cannon head to the end of its travel position.

2. Use jog operation to adjust the barrel to the top of the stroke+85 ° position.

3. Use jog operation to adjust the barrel of the gun to the straight ahead position.

4. Turn off the power switch of the control box.

5. Turn off the remote control switch.

(4) Power supply

1. The PSKD10/100WB fixed fire monitor is equipped with a DC 21.6V, 5.2Ah high-efficiency battery, which can be repeatedly charged and used without maintenance.

2. The normal operating voltage of the battery is 21.6V-25.2V. When the battery level is below 10%, the battery power decreases. To ensure reliable standby, the battery level should be checked regularly to ensure that it is above 60% charged. If it is insufficient, it should be charged in a timely manner.

3. The charger has been installed with a dedicated plug. When charging, simply connect the charger to the dedicated socket on the control box.

4. The charger comes with charging precautions, please refer to them carefully.

matters needing attention:

1. Before use, read the warning signs.

2. During spraying, personnel should try to stay away from the gun body as much as possible to ensure personal safety.

3. When operating the fire monitor, it is prohibited to press two or more buttons at the same time, and it is forbidden to operate the remote control button and control box button simultaneously to avoid program errors.

4. When using manual operation, the power should be turned off first.

5. Waste batteries and oil products need to be disposed of according to relevant national requirements to prevent pollution.