Motor energy storage:
Connect the two core DC output line to the positive and negative output sockets to the motor energy storage circuit (some mechanisms require energy storage for closing).
Control output:
Connect the three core DC output line to the opening, closing, and negative output sockets to the circuit breaker control circuit;
After startup, adjust the power supply to the required value;
Press the open (close) button to jog and control the power output
Low voltage operation test:
Connect the DC output line as above;
Set the operating voltage according to the test requirements (such as 30% or 65% of the rated voltage or other);
Press the "open/close" button to operate the power supply and observe if the switch is activated.
Millisecond meter usage:
Connect the DC output line as above;
Connect a dry node signal to the red and black signal input of the millisecond counter;
Set the operating voltage according to the test requirements (such as 30% or 65% of the rated voltage or other);
Press the "open/close" button to operate the power supply button; The millisecond counter will automatically trigger and refresh the count of the fracture signal based on whether it is a closing or opening operation, until the fracture changes, stop counting and display the final result
If a re counting operation is required, the reset button can be pressed, and the millisecond counter will return to the waiting trigger state;
1. Model: ABS chassis; Dimensions: 415 × 319 × 168 mm; Weight: 6kg;
2. Power supply voltage: AC220V; Frequency: 50Hz;
3. Environmental requirements:
Temperature: -10 ℃ to 40 ℃;
Relative humidity: ≤ 80%;
4. Insulation resistance:>2M Ω; Leakage current:<10mA;
5. Dielectric strength: The power supply incoming line can withstand a withstand voltage of 1500V (50Hz effective value) for 1 minute against the casing;
6. Working mode of DC power supply: intermittent operation. Continuous work for 2 minutes (without wind cooling), interrupted for 2 minutes;
7. Output voltage: continuously adjustable from 5 to 270V;
8. Rated current: 10A continuous; High current: 20A instantaneous;
9. Load change rate: ≤ 1%;
10. Millisecond meter: Range: 1~100000000ms; Resolution: 1ms; Degrees<=1ms;