adopt standards
HJ/T75—2007Technical Specification for Continuous Monitoring of Flue Gas Emissions from Fixed Pollution Sources
HJ/T76-2007 Technical Requirements and Monitoring Methods for Continuous Monitoring System of Flue Gas Emissions from Fixed Pollution Sources
GB13223-1996 "Emission Standards for Air Pollutants from Thermal Power Plants"
Main technical parameters
Monitoring of smoke and dust concentration
Method: Backscatter method
Measurement range: (0-500~1000) mg/m3 (range can be modified)
Zero drift: ≤± 2.0% F.S
Range drift:≤±2.0%F.S.
Output signal type: (4-20) mA/(0-10) V
Sampling method: direct measurement, no sampling required
Continuous smoke monitoring
SO2
Measurement range: (0-71500) mg/m3 (range can be modified)
Zero drift: ≤± 2.0% F.S
Range drift:≤±2.0%F.S
Response time:<180S
O2
Measurement range: (0-25)%
Resolution:0.1%
Zero drift: ≤ 2.0% F.S
Range drift:≤2.0%F.S
Response time:<180S
NO
Measurement range: (0-7150) mg/m3 (range can be modified)
Zero drift: ≤ 2.0% F.S
Range drift:≤2.0%F.S
Response time:<180S
Temperature, pressure, and flow rate monitoring of flue gas
flow velocity
Method: Micro pressure differential pitot tube method
Measurement range: (0-40) m/s
Resolution: 0.1m/s
temperature
Method: Pt100
Measurement range: (0-500) ℃
Measurement accuracy: ≤ 3 ℃
pressure
Method: Differential pressure sensor
Measurement range: (-20~+20) kPa
Instrument usage environment
Temperature: (-20~50) ℃, optimal working temperature: (22~25) ℃
Best operating temperature: (22-25) ℃
Output format: (4~20) mA, RS232
Power supply: AC220V ± 22V, 50Hz
Computer monitoring software
Store data for over ten years
Formulate reports and curves in national standard format
Display various working statuses of the system
Remote transmission via wired or wireless means