Nanjing Aiyi Technology Co., Ltd
Home>Products>AF110-R infrared combustible gas detector
Firm Information
  • Transaction Level
    VIP member
  • Contact
  • Phone
    17705175021
  • Address
    13, Kaiteng Industrial Park, Liandong U Valley, Qingshuiting East Road, Jiangning District, Nanjing City, Jiangsu Province#
Contact Now
AF110-R infrared combustible gas detector
AF110-R infrared combustible gas detector
Product details

Product Introduction

The AF110-R (three wire system)/AF111-R (bus system) combustible gas detection alarm uses the NDIR infrared principle to detect combustible gases, and is a point type combustible gas detector with a measurement range of 0-100% LEL. The product is suitable for detecting the content of hydrocarbon combustible gases in explosive hazardous areas. The product adopts an integrated design of sound and light alarm, which can effectively warn of various gas leakage hazards; Modular design, easy to maintain; The product is equipped with an infrared remote control, which can achieve complete lid free operation. The IP66 protection level is suitable for various harsh environments.

Advantages of NDIR Infrared Principle

When a substance is irradiated by an infrared beam, its molecules absorb a portion of the infrared light energy and convert it into another type of energy, namely the vibrational and rotational energy of the molecule. During the absorption process, the vibration frequency of molecules is related to their characteristics, and infrared beams are only absorbed outside the wavelengths corresponding to these frequencies. Specific substances absorb infrared light of specific wavelengths, and the concentration determines how much infrared light is absorbed. So, the type of gas can be determined based on the infrared band absorbed by the gas; Determine the gas concentration based on its absorption of infrared electromagnetic wave energy in that wavelength band. Compared to the principle of catalytic combustion, the infrared principle has the following advantages:
1. Long lifespan: Because infrared sensors detect gases without medium loss, their lifespan generally depends on the lifespan of the infrared light source, which is much higher than the principle of catalytic combustion.
2. Non poisoning: Catalytic combustion combustible gas detectors are extremely prone to poisoning and failure in environments containing elements such as silicides and sulfides, while infrared combustible gas detectors are not affected.
3. No need for oxygen: Infrared sensors detect changes in gas physical quantities and do not experience low detection values due to low oxygen in the environment.
4. Good selectivity: It only reacts with combustible gases such as hydrocarbons.
5. Wide measurement range: The range of gas detection can reach 0-100% vol, and there will be no sensor damage caused by high concentration impact.

红外可燃气体检测仪报警仪 100%LEL点型可燃气体探测器

Product Features

  • Integrated design of sound and light alarm and numerical display.
  • Modular design, ready to use, makes maintenance more convenient.
  • Made of stainless steel and aluminum alloy, the entire meter has a protection level of IP66 and is suitable for harsh environmental conditions.
  • High brightness OLED display screen, LED status indicator light, rich prompt information.
  • Built in dual switch capacity, capable of multi-level interlocking.
  • Full Chinese menu, infrared remote control operation, no need to open the lid on site.

Technical Parameter

describe parameter AF110-R AF111-R
Detect gas


combustible gas infrared
performance


detection range 0-100%LEL
Typical response time* T90≤30S
linear accuracy* ≤±5%FS
repeatability* ≤2%FS
Electrical characteristics


power supply 18-28VDC (standard 24VDC)
Product power consumption ≤3.5W
output signal 4-20mA -
RS485 -
Connection Three-wire -
Bus system -
Using cables RVVP3*1.5mm2 -
RVVP4*1.0mm2 -
Relay 2 sets of passive relays (250VAC/5A 30VDC/5A)
Display and operation


display OLED display
pilot lamp Power supply, malfunction, alarm, infrared
operating mode Infrared remote control operation
Environmental


protection grade IP66
operation temperature -40℃~70℃
Working humidity 10-95% RH non condensing
Working pressure 80-120kPa
Structural characteristics


Main material ADC12 aluminum alloy+316L stainless steel
Threaded interface NPT1/2
weight About 2.3kg
size 184*220*99mm(H*W*D)
Note: Different gas products may have differences. Please consult the manufacturer for details.



微信图片_20201217153035.jpg

20160715184048608423.jpg微信图片_20201217153045.jpg艾伊科技_04.jpg


Gas detection analyzer, dust detector, gas detection alarm, oxygen content analyzer, oxygen analyzer, oxygen analyzer
Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!

Successful operation!