8AI acquisition module
ADM-4280-C is an 8-channel 0~20mA/4-20mA/0-10V analog signal data acquisition module, which can be widely used for signal acquisition and monitoring o
Product details
Product Introduction
ADM-4280-C is an 8-channel 0~20mA/4-20mA/0-10V analog signal data acquisition module, which can be widely used for signal acquisition and monitoring of industrial field equipment. When "C" is I20, it represents an analog input of 0~20mA/4-20mA current. When "C" is V10, it represents an analog input voltage of 0-10V. The analog signal adopts a single ended input method, and the communication interface adopts RS-485 interface. It supports the standard MODBUS-RTU protocol and can be directly connected to configuration software, PLC, DCS industrial control touch screen, etc.
Product Specifications
(1) Analog input
1. Input channel: 8 single ended inputs
2. Input range: C=I20: 0~20mA/4-20mA current signal
C=V10:0~10V voltage signal
3. ADC resolution: 16 bits, reduced to 15 bits for use
4. Conversion rate: 10 times/second (full channel)
5. Measurement accuracy: better than ± 0.1%
6. Sampling resistance: 12 ohms/0.1% (current)
(2) Communication interface
1. Communication protocol: MODBUS-RTU protocol
2. Interface type: Optoelectronic isolation RS-485 interface
3. Interface protection: 600W surge protection, 15KV ESD protection, 1500V isolation protection
3. Baud rate: 1200/2400/4800/9600/19200/38400/57600/115200 BPS
4. Check bits: no check, even check, odd check
5. Default parameters: 9600, N, 8, 1 (baud rate and parity can be modified)
(3) System parameters
1. Module size: 104mm x 72mm x 26mm
2. Installation method: 35mm DIN rail installation
3. Working environment: Temperature: -10~60 ℃ Humidity: 0-95%, non condensing
4. Working power supply: DC9~30V less than 1W
Definition of module indicator lights
1. POWER: Power status indicator, constantly on/normal power supply
2. COMM: RS-485 interface communication indication, flashing/module is sending and receiving data
Use default communication parameters
When the communication parameters of the module (module address, baud rate, parity) are forgotten, short-circuit the Initiat and VS - pins and power on the module again. At this time, the module uses the initial communication parameters (9600, N, 8, 1, address 01) for communication.
When the Initiat and VS pins are disconnected, the module communicates using the communication parameters set by the user.
Module Register Address Description
1.30001~30008: Analog input register address (3x area), representing 0000H~0007H using the 04 function code.
2.40001~40008: Analog input register address (4x area), representing 0000H~0007H using the 03 function code.
3.40161~40164: Module parameter register address (4x area), for 00A0H~00A3H with 03 and 06 function codes.