Home>Products>450KW Dongfeng Cummins generator set
Product Groups
Firm Information
  • Transaction Level
    VIP member
  • Contact
  • Phone
  • Address
Contact Now
450KW Dongfeng Cummins generator set
The 450KW Dongfeng Cummins Cummins engine has a small size, light weight, low fuel consumption, reliable operation, and easy supply and maintenance of
Product details
Parameters of diesel generator set:
model FFDL-C450GF Unit power (KW) 450
Output voltage (V) 400/230 Rated output current (A) 810
wiring method three-phase four-wire power factor 0.8 (lag)
Startup method 24V DC power start Frequency (Hz) 50
Unit weight (kg) 3000 Unit size (reference value) 3198*1350*1860mm
Altitude (m) 1500 Steady-state voltage regulation rate ≤±2.5%
Steady-state frequency adjustment rate ≤±5% Steady state voltage fluctuation rate ≤±1%
Steady-state frequency fluctuation rate ≤±0.5% Transient voltage regulation rate -15%~+20%
Transient frequency adjustment rate -10%~+10% Voltage stabilization time ≤1S
diesel engine parameters
Diesel engine brand Dongfeng Cummins model QSZ13-G10
Rated speed (pm) 1500 power (kW) 463/509
Number of cylinders 6 cylinders Cylinder arrangement method in-line
Cylinder diameter * stroke (mm) 130*163 compression ratio 17.73:1
speed regulation method electronic speed control Oil supply method direct injection
fuel China 0 # Light Diesel Oil Fuel consumption rate (g/kw. h) ≤196
intake method Boosting and intercooling Oil consumption rate (g/kw. h) ≤4
Steady-state speed regulation rate ≤5% emission standard National Computer Rank Examination Grade 2
cooling method Satisfy the ambient temperature of 40 ℃ with a radiator for the water tank, a belt driven cooling fan, and a fan safety cover
Motor parameters
Motor brand Feng Fa Motor model FFH-450
Rated power (KW) 450 Rated voltage (V) 400/230
Rated speed (pm) 1500 Rated frequency (Hz) 50
excitation method brushless self-excitation material 100% pure copper wire manufacturing
Protection level IP23 insulation class H
wiring method Three phase four wire Y-shaped winding adjustment method AVR (Automatic Voltage Regulator)
Calibration environment
·Environmental temperature: ≤ 40 ℃ · Relative humidity: ≤ 60% · Altitude: ≤ 1000m
·Meets the requirements of ISO3046 and ISO8528.
Optional configuration
·ATS Automatic Load Conversion Cabinet · Automatic Parallel Operation Cabinet (Deep Sea DSE Control Module)
·Container type generator set
·Mobile trailer type power station
·Rainproof cover type generator set
·Silent mobile power station
·Remote microcomputer interface
·Running 500-1000 hours with spare parts
Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!

Successful operation!